Only timer with Screw less vibration proof
terminals (Also ideal to use for Specialized applications).
Wireless interiors makes it highly rugged
& error proof.
Uses Digital IC's to give accurate repeat
cycles.
Professional design (terminals at the rear
end) makes it ideal to use as a flush mounting timer with
MCB type fitting as well as on any standard mounting channel.
Calibrated dial
with 5% Accuracy
Only Adjustable
Cyclic Time with User Selectable ON & OFF Sequence.
Technical
Data
Output contacts
:
2 change over contacts. (2 separate
contact in case of GT1-SD and GT1-ID)
Switching Duty
:
6A Resistive at 240V AC or 24V
DC.
Electrical Life
:
10^5 Operations at switching
duty.
Operating Voltage
:
110V / 230 / 415 AC or 12 /
24 DC
Permissible Voltage
:
25% Max
Power Consumption
:
10VA (max.).
Reset Time
:
100 m. sec. max.
Repeat Accuracy
:
0.5% Full Scale
Setting Accuracy
:
5% of Full Scale.
LED Indications
:
a) Power on
b) Relay on
c) Relay off (for adj. cyclic Timer only).
Mounting
:
Any standard mounting channel.
Dimensions
:
40mm(W) * 90mm(H) * 110mm(D)
Operation
GT1 - ON (On
Delay timer) When operating voltage is applied to terminals,
the timing is initiated and relay shall energises at the end
of timing set on dial. To reset, switch-off the supply.(fig-1)
GT1 - IN (Interval
timer) On applying the operating voltage to supply terminals
the relay is energised instantly and de-energises at the end
of timing set on dial.(fig-1)
GT1 - EC (Equal
Cyclic timer) On applying the operating voltage to supply
terminals the relay energises and de-energises at the same intervals
as timing set on dial.(fig-3)
GT1 - AC (Adjustable
Cyclic timer) On applying the operating voltage to supply
terminals the relay energises after the 'OFF TIME' set on the
dial and remains energised until the 'ON TIME' set on the dial.
The sequence goes on till the supply is available on terminals.
'ON' and 'OFF' time can be set individually.(fig-4)
GT1 - ACM (Adjustable
Cyclic Multi Range timer) This is an adjustable Cyclic Timer
with Multi Time Range. The sequence of ON and OFF is user selectable
viz. relay ON first or OFF First.(fig-5)
GT1 - ID (Instantaneous
Delayed timer) On applying power supply RL1 (Inst.) will
energise Instantly and RL2 (delayed) will energise after the
Time Delay SET on dial.(fig-6)
GT1 - SD (Star-Delta
timer) On applying operating voltage of supply terminals.
The star relay energises instantly. After the completion of
time delay on dial the star relay de-energises and Delta relay
energises after fixed pause (60ms 10ms) time. It ensures smooth
change over. The time range is 30sec./60sec. (fig-7)
Note:- Design and specifications may change due to our continuous