Power Protection - Voltage Relays
1
2
   
   
   
   
 
 
3

  Special Features
 
Available with Pick-up and Trip Time Delay in 3-Phase Voltage Relays
Smart design to fit on any standard mounting channel
Choice of screw less terminals
 
2% Accuracy
  Test and Auto/Manual Reset facility
  Signal and Source (Control supply) are separate
  Designed for high reliability, as relay energizes only under fault conditions
  Only 1/2 phase voltage relay with user selectable U/V or O/V range by DIP switch
  Only 1/2 phase voltage relay with 2 user selectable voltage range by DIP switch
  Technical Data
Supply Voltage
:
110V/220V/380V/440V AC 50Hz or 12/24V DC
Permissible Supply Variation
:
25%
Output Contacts : 2 change over contacts (2 sets, one for each set points in case of 2S Relays)
Switching Duty : 6A resistive at 24V DC or 240V AC
Relay Status : De-energized in normal conditions
Set Point (Range) : a)VR1-1/VR1-2 = 180-220 & 240-300/340-400 &    440-500 V AC
b)VR96-1 = 180-220 & 240-300/340-400 & 440-500
   V AC
c)VR3-3/VR3-4 = 340-400 & 440-500 V AC
Time Delay (optional) : 0.1-10 sec settable
Mode of Operation : Under Voltage/Over Voltage (user selectable) & U/V-O/V combined.
Reset : Automatic/Manual
Setting Accuracy : 5% of Full Scale
Mounting : Any standard mounting channel
Dimensions : 77mm(W) * 90mm(H) * 110mm(D) for 2S models - 155mm(W) For VR96-1 = 96mm(W) * 96mm(H) * 70mm(D)
  Operation
VR1-1 / VR1-2: The 1ph/2ph. voltage relay monitors the voltage signal (to be connected at sensing point) when the signal goes out of the range selected on the dial, the status of relay will change. The relays are available with or without time delays. In case of relays with time delay 'SET' LED will glow when voltage signal goes out of the range selected. the relay will energized after delay and is also indicated by 'RLY' LED.
VR3-3 / VR3-4: The 3ph. voltage relay continuously sense the voltage level of each phase individually, thus if any of the phase goes out of the range selected on 'Voltage Set' dial, it will change the status of relay. It will also indicate that voltage of which phase have gone under or over the range by separate LEDS. The HEALTHY LED Glows when voltage level is within the voltage range selected. The relay will energize in fault condition after the 'PICK-UP' time delay and will de-energizes after 'TRIP' time delay when normal conditions resumes.
* Relays with Two set point can be used for two separate relay contacts of under and over voltage protection for same source.

Note:- Design and specifications may change due to our continuous developmental efforts.

   